Damper

Dampers control the flow of air.

Damper can either be:

  • Components of a larger entity (AHU, VAV, etc)
  • Stand-alone components (Floor Damper, inline damper in duct)
    • An argument could be made that stand alone dampers are VAVs; however we have made the distinction that VAVs will have additional sensors (esp. with regards to zone control) that a standalone damper may not have

At this time we are not validating against this distinction, but we will do in future.

Variations

Nil


Composition

Core

Nil

Switch

Nil

Relationships

Core

Nil

Switch

Nil

Switch does not require modelling components beyond the damper entity.

Points

All

An entity of this type is expected to have a selection of points from this provided list. Any points assigned that are not on this list will throw a warning.

switch:hasPointNamesh:class
Run CommandOn_Off_Command
Run StatusOn_Off_Status
Enable CommandEnable_Command
Enable StatusEnable_Status
ModeMode_Status
Occupancy CommandOccupancy_Command
Occupancy ModeOccupied_Mode_Status
Override Modeswitch:OverrideMode Status
Pressure Reset Modeswitch:Pressure_Reset_Operating_Mode_Status
Out of Service Statusswitch:Maintenance_Mode_Enable_Status
Fault Modeswitch:Fault_Mode_Status
Fault StatusFault_Status
Air TemperatureAir_Temperature_Sensor
Air Temperature SetpointAir_Temperature_Setpoint
Air HumidityRelative_Humidity_Sensor
Air Absolute HumidityHumidity_Sensor
Air PressureStatic_Pressure_Sensor
Air Pressure SetpointStatic_Pressure_Setpoint
Air FlowAir_Flow_Sensor
Air Flow SetpointAir_Flow_Setpoint
Air Velocity
PositionPosition_Sensor
Position Setpointswitch:Position_Setpoint
Position CommandPosition_Command
Position Low Limit Setpointswitch:Position_Low_Limit_Setpoint
Position High Limit Setpointswitch:Position_High_Limit_Setpoint
Position Statusswitch:Position_Status
Open Command
Close Command
Flow RateFlow_Sensor
Flow Statusswitch:Flow_Status
Delta-PDifferential_Pressure_Sensor
Delta-P High Limit Setpointswitch:Differential_Pressure_High_Limit_Setpoint
Delta-P Low Limit Setpointswitch:Differential_Pressure_Low_Limit_Setpoint
CO2CO2_Sensor
Index Pressureswitch:Index_Static_Pressure_Sensor

Minimum Set

The minimum selection of points Switch Automation expects to see on an entity of this type.

ONE point from the following list:

switch:hasPointNamesh:class
PositionPosition_Sensor
Position Setpointswitch:Position_Setpoint
Position CommandPosition_Command
Position Statusswitch:Position_Status

::Other Sets...::